Analyser Chauvin Arnoux C.A 8335 can measure harmonics of electrical network. In previous article was described how to measure transients in power grid by using Analyser Chauvin Arnoux C.A 8335.

 

The sequence of measuring harmonics:

  1. Powering of analyser.
  2. Connecting voltage and current leads.
  3. Setting of measurement scheme.
  4. Setting of measurement method.
  5. Setting of date and time.
  6. Connecting scheme of analyser.
  7. Measuring of harmonics.

 

  1. Powering of analyser.

Turn on analyser:

A2-1

 

 

  1. Connecting of voltage and current leads.

It‘s time to connect voltage and current leads to analyser.

Press „Setting“ button:

A2-2

 

By using „up“, „down“ buttons select option “Sensors and rations”:

Chauvin Arnoux 8335

 

Press yellow button below letter „A“ as marked in picture:

A2-4

 

At this moment current leads (clamps) are not connected yet:

Chauvin Arnoux 8335

 

Every current clamp has own color marking: phase A (or L1) – yellow, phase B (or L2) – green, phase C (or L3) – red. Neutral current clamp is marked as blue.

 

Phase A current clamp:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Analyser has recognised phase A current clamp after connecting clamp to analyser’s socket:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Chauvin Arnoux 8335

 

Connect other current clamps to analyser:

A2-9

 

Connect voltage A, B, C leads to analyzer:

Chauvin Arnoux 8335

 

  1. Setting of measurement scheme.

Press „Setting“ button:

A2-11

 

By using „up“, „down“ buttons select option “ Electrical connection ” scheme as shown in picture:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

By using „up“, „down“ buttons select electrical connection scheme as shown in picture:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Press button „Enter“:

A2-14

 

  1. Setting of measurement method. Here you can select measurement method with harmonics.

By using „up“, „down“ buttons select option “Calculation methods ” as shown in picture:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Chauvin Arnoux 8335

Press button  “Enter”.

 

  1. Date and time setting.

 

We need to set date and time:

Press button „Settings.

By using „up“, „down“ buttons select „Date/Time“.

Press button „Enter“.

Set correct date and time.

Press button „Enter“.

 

  1. Connecting scheme of analyser.

This scheme is shown in picture:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

You should pay atention that direction of current clamp should be the same as flowing current direction in phase.

Chauvin Arnoux 8335

If these directions will be oposite, measurements of currents will be not correct (current will be shifted by180°).

Connected current clamps:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Connected voltage clamps:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

  1. Measuring harmonics.

Press button as shown in picture:

A2-21

Chauvin Arnoux 8335

 

Press yellow button below letter A.

Current harmonics:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

Press yellow button below letter V.

Voltage harmonics:

Chauvin Arnoux 8335

 

Current and voltage harmonics opened with analyser’s software:

Chauvin Arnoux 8335

 

Chauvin Arnoux 8335

 

Press button as shown in picture:

A2-26

 

Here we can analyse waveforms of voltages and currents:

Chauvin Arnoux 8335

 

Chauvin Arnoux 8335

 

Waveforms of voltages:

Chauvin Arnoux 8335

 

Chauvin Arnoux 8335

 

We can  download received waveforms to PC.

You can make picture of this waveform.

Press button „Snapshot“ and hold it pressed for several seconds:

A2-31

 

On upper left corner will apear „camera“ picture:

Chauvin Arnoux 8335

 

Photo is made.

Opening photo of waveform.

Press button „Snapshot“:

A2-33

In window „Snapshot list“ select photo and open it:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Opening waveforms by PC.

„Power analyzer“ software is used to open recorded waveforms.

Install „Power analyzer“ software and run it.

Press button „Connect“:

A2-36

 

Set connection parameters:

A2-37

 

Window „Instrument“:

A2-38

 

Select “Photographs” option and open selected record:

Chauvin Arnoux 8335

 

Current waveforms:

A2-40

Chauvin Arnoux 8335

 

Current harmonics:

Chauvin Arnoux 8335

Chauvin Arnoux 8335

 

Voltage waveforms:

A2-42

 

Voltage harmonics:

A2-43

Voltage (black) and current (yellow) waveforms of phase L1:

Chauvin Arnoux 8335

Voltage (red) and current (green) waveforms of phase L2:

A2-45

Voltage (blue) and current (red) waveforms of phase L3:

A2-46

As you can see in this article measured current harmonics are huge. Voltage harmonics are small. In most cases in power network exist only current harmonics.